Application and Design
EVH-660D is a Florida Product Approved and Miami-Dade Qualified stationary
vertical blade wind driven rain extruded aluminum louver designed to protect
air intake and exhaust openings in building exterior walls. EVH-660D is tested
in accordance with AMCA 500-L Air Performance, Water Penetration and Wind
Driven Rain. EVH-660D is tested in accordance with AMCA 540 Test Method for
Louvers Impacted by Wind Borne Debris (Basic Protection, Missile Level D and
Enhanced Protection, Missile Level E). EVH-660D is tested in accordance with
AMCA 550 Test Method for High Velocity Wind Driven Rain Resistant Louvers.
EVH-660D is licensed to bear the AMCA seal allowing design professionals
to select and apply with confidence. EVH-660D is tested and qualified per
the following Florida test protocols: TAS 201 (Large Missile Impact), TAS 202
(Uniform Static Air Pressure), TAS 203 (Cyclic Wind Loading) and TAS 100A
(Wind Driven Rain). Per Miami-Dade EVH-660D may be installed in locations
where the room behind the louver is NOT designed to drain water penetrating
into the room or the room will house non-water resistant or water proof
equipment components or supplies.
Standard Construction
Frame � � � � � � � � � � Heavy gauge extruded 6063T5 aluminum,
6 in. x 0.095 in. nominal wall thickness
Blades � � � � � � � � � � Vertical rain resistant design, heavy gauge extruded
6063T5 aluminum, 0.063 in. nominal wall thickness,
positioned on approximately 0.75 in. centers
Construction . . . . . Mechanically fastened
Birdscreen � � � � � � � 3/4 in. x 0.051 flattened expanded aluminum
removable frame, inside mount (rear)
Finish � � � � � � � � � � � Mill
Anchor Clips � � � � � Heavy gauge extruded aluminum, mill finish,
continuous mounting angels (head and sill only)
Minimum Rough
Opening Size � � � � 12 in. W x 12 in. H
Maximum Rough
Opening Size � � � � Unlimited W x 120 1/2 in. H
Maximum Rough Opening Single
Section Size � � � � � 48 1/2 in. W x 120 1/2 in. H
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panels
• Extended sill
• Filter racks
• Flanged frame
• Security bars
• Factory attached VCD-40 damper
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel
Kynar
*Width and height dimensions furnished
approximately 1/2 inch under size.
Miami-Dade Qualified
Wind-Driven Rain Louver
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
EVH-660D
NOTE: Lifting lugs will be shipped with all units over 10 sq. ft.
EVH-660DPERFORMANCE DATA
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
The AMCA Water Penetration Test provides a method for comparing various
louver models and designs as to their efficiency in resisting the penetration
of rainfall under specific laboratory test conditions. The beginning point of
water penetration is defined as that velocity where the water penetration curve
projects through 0.01 oz. of water (penetration) per sq. ft. of louver free area.
*The beginning point of water penetration for Model EVH-660D is above
1250 fpm free area velocity. These performance ratings do not guarantee a
louver to be weather-proof or stormproof and should be used in combination
with other factors including good engineering judgement in selecting louvers.
Airflow Resistance (Standard Air - �075 lb/ft
3
)
Model EVH-660D resistance to airflow (pressure drop) varies
depending on louver application (air intake or air exhaust). Free area
velocities (shown) are higher than average velocity through the overall
louver size. See louver selection information. (Test Figure 5.5-6.5)
Weather louvers shall be classified by their ability to reject simulated rain. The
table shows different classifications based on the maximum simulated rain
penetration per square meter (square feet) of louver. Water penetration rating
at a given louver face velocity is determined by the water penetration while
the louver is subjected to a selected simulated rainfall rate and wind velocity.
Wind-Driven Rain Performance
Discharge Loss Coefficient Class (Intake) = 2
Water Penetration
Test Size 48 in� x 48 in� Test Duration of 15 min�
Discharge Loss Coefficient Classifications
Wind-driven Rain
Penetration ClassesClass Discharge Loss Coefficient
1 0.4 and Above Class Effectiveness
2 0.3 to 0.399 A 1 to 0.99
3 0.2 to 0.299 B 0.989 to 0.95
4 0.199 and Below C 0.949 to 0.80
D Below 0.80
Greenheck Fan Corporation certifies that the
EVH-660D louvers shown herein are licensed
to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Program. The
AMCA Certified Ratings Seal applies to air
performance, water penetration, and wind-
driven rain ratings.
Greenheck Fan Corporation certifies that the EVH-660D louvers
shown herein are approved to bear the AMCA Listing Label. The
Ratings shown are based on tests and procedures performed
in accordance with AMCA Publications and comply with the
requirements of the AMCA Listing Label Program. The AMCA
Listing Label applies to Wind Borne Debris Impact Resistant and
High Velocity Rain Resistant Louvers.
75 mm/h (3 in./hr) Rainfall &
13 m/s (29 mph) Wind Velocity
202 mm/h (8 in./hr) Rainfall &
22 m/s (50 mph) Wind Velocity
Free Area Velocity
Ventilation Air Core
Velocity
Water Penetration Free Area Velocity
Ventilation Air Core
Velocity
Water Penetration
(fpm) (m/s) (fpm) (m/s) Effective Class (fpm) (m/s) (fpm) (m/s) Effective Class
0.0 (0) 0.0 (0) A 0.0 (0) 0.0 (0) A
0.9 (185) 0.5 (98) A 0.9 (185) 0.5 (98) A
1.9 (371) 1.0 (197) A 1.9 (371) 1.0 (197) A
2.8 (556) 1.5 (295) A 2.8 (556) 1.5 (295) A
3.8 (742) 2.0 (394) A 3.8 (742) 2.0 (394) A
4.7 (927) 2.5 (492) A 4.7 (927) 2.5 (492) A
5.7 (1113) 3.0 (591) A 5.7 (1113) 3.0 (591) A
6.6 (1298) 3.5 (689) A 6.6 (1298) 3.5 (689) A
7.5 (1483) 4.0 (787) A 7.5 (1483) 4.0 (787) A
8.5 (1669) 4.5 (886) A 8.5 (1669) 4.5 (886) A
9.4 (1852) 5.0 (983) 100.0 A 9.4 (1856) 5.0 (985) 100.0 A
EVH-660DPERFORMANCE DATA
Free Area Chart (sq. ft.)
Core Area Chart (sq. ft.)
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
Louver
Height
Inches
Louver Width in Inches
12 18 24 30 36 42 48
12 0.17 0.34 0.52 0.70 0.88 1.06 1.23
18 0.30 0.63 0.95 1.27 1.60 1.92 2.24
24 0.44 0.91 1.38 1.84 2.31 2.78 3.25
30 0.58 1.19 1.80 2.42 3.03 3.65 4.26
36 0.71 1.47 2.23 2.99 3.75 4.51 5.27
42 0.85 1.75 2.66 3.56 4.47 5.37 6.28
48 0.98 2.03 3.09 4.14 5.19 6.24 7.29
54 1.12 2.32 3.51 4.71 5.90 7.10 8.29
60 1.26 2.60 3.94 5.28 6.62 7.96 9.30
66 1.39 2.88 4.37 5.85 7.34 8.83 10.31
72 1.53 3.16 4.79 6.43 8.06 9.69 11.32
78 1.67 3.44 5.22 7.00 8.78 10.55 12.33
84 1.80 3.73 5.65 7.57 9.49 11.42 13.34
90 1.94 4.01 6.08 8.14 10.21 12.28 14.35
96 2.08 4.29 6.50 8.72 10.93 13.14 15.36
102 2.21 4.57 6.93 9.29 11.65 14.01 16.37
108 2.35 4.85 7.36 9.86 12.37 14.87 17.37
114 2.48 5.13 7.78 10.43 13.08 15.73 18.38
120 2.62 5.42 8.21 11.01 13.80 16.60 19.39
Louver
Height
Inches
Louver Width in Inches
12 18 24 30 36 42 48
12 0.44 0.73 1.03 1.33 1.62 1.92 2.22
18 0.80 1.35 1.90 2.44 2.99 3.54 4.09
24 1.17 1.97 2.77 3.56 4.36 5.16 5.95
30 1.54 2.59 3.63 4.68 5.73 6.77 7.82
36 1.91 3.20 4.50 5.80 7.09 8.39 9.69
42 2.27 3.82 5.37 6.91 8.46 10.01 11.56
48 2.64 4.44 6.24 8.03 9.83 11.63 13.42
54 3.01 5.06 7.10 9.15 11.20 13.24 15.29
60 3.38 5.67 7.97 10.27 12.56 14.86 17.16
66 3.68 6.19 8.69 11.20 13.70 16.21 18.71
72 4.05 6.81 9.56 12.32 15.07 17.83 20.58
78 4.42 7.42 10.43 13.43 16.44 19.44 22.45
84 4.79 8.04 11.30 14.55 17.81 21.06 24.32
90 5.15 8.66 12.16 15.67 19.17 22.68 26.18
96 5.52 9.28 13.03 16.79 20.54 24.30 28.05
102 5.89 9.89 13.90 17.90 21.91 25.91 29.92
108 6.26 10.51 14.77 19.02 23.28 27.53 31.79
114 6.62 11.13 15.63 20.14 24.64 29.15 33.65
120 6.99 11.75 16.50 21.26 26.01 30.77 35.52
EVH-660DINSTALLATION DETAILS
Maximum Size and Installation Information
Model EVH-660D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the installation instructions shown herein.
Model EVH-660D is qualified for installation within concrete/masonry, steel stud, structural steel or wood framed building conditions. Model EVH-660D is structurally
calculated to withstand positive and negative wind-loads up to 150 PSF. The maximum single section width is 48 in. The maximum single section height is 120 in.
While the maximum section height is limited to 120 in., the width may be unlimited as multiple sections may be installed side by side in accordance with installation
instructions. Structural reinforcing members along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck.
Options and are not subject to structural analysis unless indicated otherwise by Greenheck.
Minimum
Rough Opening Size
12 in� W x 12 in� H
Maximum Rough Opening
Single Section Size
48 1/2 in� W x 120 1/2 in� H
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
PRODUCT DETAILS EVH-660D
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
Optional VCD-40 Control Damper
FASTENER CHART EVH-660D
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
DESCRIPTION
SUBSTRATE
EDGEDISTANCE<MIN> 1IN 11/2IN 21/2IN
PENETRATION<MIN>
LOUVERHEIGHT<IN>
>108&≤120
2
>96&≤108
>72&≤96
>48&≤72 4
>0&≤48 6
6
4
6
1/4"TAPCONSCREWFASTENERTABLE
CONCRETEORCMUANCHORING
4
1/4"TAPCON
CONCRETEORCMU(GROUTFILLED)
13/4IN
SPACING<IN>
MINIMUM 3.192KSICONCRETEOR3.192KSIGROUT
2
DESCRIPTION
SUBSTRATE
EDGEDISTANCE<MIN> 2IN 3IN 41/2IN 11/2IN
2IN
PENETRATION<MIN>
LOUVERHEIGHT<IN>
>108&≤120
4
>72&≤108
>36&≤72
>0&≤36 6
6
6
6
21/8IN 21/2IN
SPACING<IN> SPACING<IN>
6
NOTALLOWED
NOTALLOWED
3/8"POWERSWEDGEBOLTFASTENERTABLE
CONCRETEORCMUANCHORING
MINIMUM 2.5KSI
6"WIDE,GRADEN,TYPEII,
LIGHT/MEDIUM/NORMALWEIGHT
CMUCONFORMINGTOASTMC90
NORMALWEIGHTCONCRETE CMU<1.5KSIGROUTFILLED>
3/8"POWERSWEDGEBOLT
DESCRIPTION 3/8"LAGSCREW 1/4"LAGSCREW
SUBSTRATE
MINIMUM
EDGEDISTANCE<MIN>
PENETRATION<MIN> 16GA<0.06IN> 3/16IN
LOUVERHEIGHT<IN>
>84&≤120
4
>0&≤84
6
G≥0.42
WOOD OR STEELANCHORING
LAGSCREW,SCREW,&BOLTW/NUTFASTENERTABLE
1/4"20SCREWORBOLTW/NUT
STEEL
A36STEELORFy36KSI
WOOD
1/2IN
SPACING<IN>
66
23/4IN
SPACING<IN>
11/2IN
EVH-660D
September 2021
Copyright © 2021 Greenheck Fan Corporation
Greenheck Fan Corporation reserves the right
to make product changes without notice�
OPTION DRAWINGS EVH-660D
Florida Product Approval No.: 16785.1
Miami-Dade, FL NOA No.: 21-0526.07 EXP. 10/4/22
AMCA 540 and 550 Listed
TDI Approval No.: LVR-07
Maximum Wind-load: 150 PSF
Finish Type Description/Application Color Selection
Standard Warranty
(Aluminum)
AAMA 2605
100% Fluoropolymer (FEVE)
2-Coat 70% Kynar
®
(PVDF)
3-Coat 70% Kynar
®
(PVDF)
4-Coat 70% Kynar
®
(PVDF)
“Best.” The premier finish for extruded aluminum. Tough,
long-lasting coating has superior color retention and
abrasive properties. Resists chalking, fading, chemical
abrasion and weathering.
Standard Colors:
Any of the 27 standard colors shown can be furnished
in 70% or 50% Kynar
®
, 100% Fluoropolymer or Baked
Enamel.
Mica Colors:
Greenheck offers 6 standard Mica colors for 70%
Kynar
®
or 100% Fluoropolymer.
Custom Colors:
Custom color matching is available. Consult your
Greenheck representative for cost and/or lead-time
implications if a custom color is required.
10 Years
(20 Years Optional)
AAMA 2604
50% Kynar
®
/ Acroflur
®
“Better.” Tough, long-lasting coating has excellent color
retention and abrasive properties. Resists chalking, fading,
chemical abrasion and weathering.
5 Years
AAMA 2603
Baked Enamel
“Good.” Provides good adhesion and resistance to
weathering, corrosion and chemical stain.
1 Year
AA-M10C22A42
Integral Color Anodize
“Two-step” anodizing is produced by following the normal
anodizing step with a second, colorfast process.
Light, Medium, Dark or Extra Dark Bronze;
Champagne; Black
5 years
AA-M10C22A41
Clear Anodize 215 R-1
Clear, colorless and hard oxide aluminum coating that
resists weathering and chemical attack.
Clear 5 years
AA-M10C22A31
Clear Anodize 204
Clear, colorless and hard oxide aluminum coating that
resists weathering and chemical attack.
Clear 1 Year
Prime Coat
Louvers or architectural products shall be cleaned, pre-treated and receive a prime coat finish suitable for field
painting. Greenheck does not recommend prime coat or field painting of materials.
n/a
Mill
Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is acceptable and
there is no concern for color or color change.
n/a
Finishes meet or exceed AAMA 2605, AAMA 2604, and AAMA 2603 requirements. Please consult www.greenheck.com for complete information on standard and
extended paint warranties. Paint finish warranties are not applicable to steel products.
FINISHES