Application and Design
EVH-501D is a Florida Product Approved and Miami-Dade Qualified stationary vertical
blade wind driven rain extruded aluminum louver designed to protect air intake and exhaust
openings in building exterior walls. EVH-501D is tested in accordance with AMCA 500-L Air
Performance, Water Penetration and Wind Driven Rain. EVH-501D is tested in accordance
with AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic
Protection, Missile Level D and Enhanced Protection, Missile Level E). EVH-501D is tested
in accordance with AMCA 550 Test Method for High Velocity Wind Driven Rain Resistant
Louvers. EVH-501D is licensed to bear the AMCA seal allowing design professionals to
select and apply with confidence. EVH-501D is tested and qualified per the following Florida
test protocols: TAS 201 (Large Missile Impact), TAS 202 (Uniform Static Air Pressure) and
TAS 203 (Cyclic Wind Loading). Per Miami-Dade EVH-501D may be installed in locations
where the room behind the louver is NOT designed to drain water penetrating into the
room or the room will house non-water resistant or water proof equipment, components or
supplies.
Standard Construction
Frame � � � � � � � � � � Heavy gauge extruded aluminum,
5 in. x 0.081 in. nominal wall thickness
Blades � � � � � � � � � � Vertical rain resistant design, heavy gauge extruded 6063-T5
aluminum, 0.063 in. nominal wall thickness, positioned on
approximately 1.5 in. centers
Construction . . . . . Mechanically fastened
Birdscreen � � � � � � � 3/4 in. x 0.051 flattened expanded aluminum
removable frame, inside mount (rear)
Finish � � � � � � � � � � � Mill
Minimum Rough
Opening Size � � � � 12 in. W x 12 in. H
Maximum Rough
Opening Size � � � � Unlimited W x Unlimited H
Multi-wide assemblies are permitted without any additional
reinforcing provided the rough opening height is 120 in. or less
Multi-high assemblies are permitted provided suitable load
bearing structure is provided (by others) at each louver section(s)
head and sill condition so that the louvers section(s) may
installed in accordance with the instructions shown herein
Maximum Single
Section Size � � � � � 72 in. W x 120 in. H or 120 in. W x 72 in. H
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panels
• Extended sill
• Filter racks
• Flanged frame
• Security bars
*Width and height dimensions furnished
approximately 3/4 inch under size.
Miami-Dade Qualified
Wind-Driven Rain Louver
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
EVH-501D
• A variety of architectural finishes
including:
Clear anodize
Integral color anodize
Baked enamel paint
Kynar paint
EVH-501DPERFORMANCE DATA
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
The AMCA Water Penetration Test provides a method for comparing various
louver models and designs as to their efficiency in resisting the penetration
of rainfall under specific laboratory test conditions. The beginning point of
water penetration is defined as that velocity where the water penetration curve
projects through 0.01 oz. of water (penetration) per sq. ft. of louver free area.
*The beginning point of water penetration for Model EVH-501D is above
1250 fpm free area velocity. These performance ratings do not guarantee a
louver to be weather-proof or stormproof and should be used in combination
with other factors including good engineering judgement in selecting louvers.
Airflow Resistance (Standard Air - �075 lb/ft
3
)
Model EVH-501D resistance to airflow (pressure drop) varies
depending on louver application (air intake or air exhaust). Free area
velocities (shown) are higher than average velocity through the overall
louver size. See louver selection information. (Test Figure 5.5-6.5)
Weather louvers shall be classified by their ability to reject simulated rain. The
table shows different classifications based on the maximum simulated rain
penetration per square meter (square feet) of louver. Water penetration rating
at a given louver face velocity is determined by the water penetration while
the louver is subjected to a selected simulated rainfall rate and wind velocity.
Wind-Driven Rain Performance
Discharge Loss Coefficient Class (Intake) = 2
Water Penetration
Test Size 48 in� x 48 in� Test Duration of 15 min�
Discharge Loss Coefficient Classifications
Wind-driven Rain
Penetration ClassesClass Discharge Loss Coefficient
1 0.4 and Above Class Effectiveness
2 0.3 to 0.399 A 1 to 0.99
3 0.2 to 0.299 B 0.989 to 0.95
4 0.199 and Below C 0.949 to 0.80
D Below 0.80
Greenheck Fan Corporation certifies that the
EVH-501D louvers shown herein are licensed
to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Program. The
AMCA Certified Ratings Seal applies to air
performance, water penetration, and wind-
driven rain ratings.
Greenheck Fan Corporation certifies that the EVH-501D louvers
shown herein are approved to bear the AMCA Listing Label. The
Ratings shown are based on tests and procedures preformed
in accordance with AMCA Publications and comply with the
requirements of the AMCA Listing Label Program. The AMCA
Listing Label applies to Wind Borne Debris Impact Resistant and
High Velocity Rain Resistant Louvers.
75mm/h (3 in/hr) Rainfall & 13 m/s (29
mph) Wind Velocity
200mm/h (8 in/hr) Rainfall & 22 m/s
(50 mph) Wind Velocity
Ventilation Air
Core Velocity
m/s (fpm)
Water Penetration
Effectiveness %
Water Penetration
Classification
Ventilation Air
Core Velocity
m/s (fpm)
Water Penetration
Effectiveness %
Water Penetration
Classification
0.0 (0) A 0.0 (0) A
0.5 (98) A 0.5 (98) A
1.0 (196) A 1.0 (196) A
1.5 (295) A 1.5 (295) A
2.0 (393) A 2.0 (393) A
2.5 (492) A 2.5 (492) A
3.0 (590) A 3.0 (590) A
3.5 (688) A 3.5 (688) A
4.0 (782) 100.0 A 4.0 (787) A
4.4 (875) 99.9 A 4.4 (872) 100.0 A
5.0 (989) 99.8 A 5.0 (975) 99.9 A
EVH-501DPERFORMANCE DATA
Free Area Chart (sq. ft.)
Core Area Chart (sq. ft.)
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
Louver
Height
Inches
Louver Width in Inches
12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120
12 0.26 0.45 0.65 0.84 1.04 1.23 1.43 1.62 1.82 2.01 2.21 2.40 2.60 2.79 2.99 3.18 3.38 3.57 3.76
18 0.48 0.84 1.20 1.57 1.93 2.29 2.65 3.01 3.37 3.74 4.10 4.46 4.82 5.18 5.55 5.91 6.27 6.63 6.99
24 0.70 1.23 1.76 2.29 2.82 3.35 3.88 4.40 4.93 5.46 5.99 6.52 7.05 7.58 8.10 8.63 9.16 9.69 10.22
30 0.93 1.62 2.32 3.01 3.71 4.40 5.10 5.79 6.49 7.19 7.88 8.58 9.27 9.97 10.66 11.36 12.05 12.75 13.45
36 1.15 2.01 2.87 3.74 4.60 5.46 6.32 7.19 8.05 8.91 9.77 10.64 11.50 12.36 13.22 14.09 14.95 15.81 16.67
42 1.37 2.40 3.43 4.46 5.49 6.52 7.55 8.58 9.61 10.64 11.66 12.69 13.72 14.75 15.78 16.81 17.84 18.87 19.90
48 1.59 2.79 3.99 5.18 6.38 7.57 8.77 9.97 11.16 12.36 13.56 14.75 15.95 17.15 18.34 19.54 20.73 21.93 23.13
54 1.81 3.18 4.54 5.90 7.27 8.63 9.99 11.36 12.72 14.08 15.45 16.81 18.17 19.54 20.90 22.26 23.63 24.99 26.35
60 2.04 3.57 5.10 6.63 8.16 9.69 11.22 12.75 14.28 15.81 17.34 18.87 20.40 21.93 23.46 24.99 26.52 28.05 29.58
66 2.26 3.96 5.65 7.35 9.05 10.74 12.44 14.14 15.84 17.53 19.23 20.93 22.63 24.32 26.02 27.72 29.41 31.11 32.81
72 2.48 4.35 6.21 8.07 9.94 11.80 13.67 15.53 17.39 19.26 21.12 22.99 24.85 26.71 28.58 30.44 32.31 34.17 36.04
78 2.65 4.64 6.63 8.62 10.61 12.59 14.58 16.57 18.56 20.55 22.54
84 2.87 5.03 7.18 9.34 11.50 13.65 15.81 17.96 20.12 22.28 24.43
90 3.09 5.42 7.74 10.06 12.39 14.71 17.03 19.35 21.68 24.00 26.32
96 3.31 5.80 8.29 10.78 13.28 15.77 18.26 20.75 23.24 25.73 28.22
102 3.54 6.19 8.85 11.51 14.17 16.82 19.48 22.14 24.79 27.45 30.11
108 3.76 6.58 9.41 12.23 15.05 17.88 20.70 23.53 26.35 29.17 32.00
114 3.98 6.97 9.96 12.95 15.94 18.94 21.93 24.92 27.91 30.90 33.89
120 4.20 7.36 10.52 13.68 16.83 19.99 23.15 26.31 29.47 32.62 35.78
Louver
Height
Inches
Louver Width in Inches
12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120
12 0.51 0.80 1.09 1.39 1.68 1.97 2.26 2.55 2.84 3.14 3.43 3.72 4.01 4.30 4.59 4.89 5.18 5.47 5.76
18 0.95 1.49 2.03 2.57 3.11 3.66 4.20 4.74 5.28 5.82 6.36 6.91 7.45 7.99 8.53 9.07 9.61 10.16 10.70
24 1.39 2.18 2.97 3.76 4.55 5.34 6.14 6.93 7.72 8.51 9.30 10.09 10.89 11.68 12.47 13.26 14.05 14.84 15.64
30 1.82 2.86 3.91 4.95 5.99 7.03 8.07 9.11 10.16 11.20 12.24 13.28 14.32 15.36 16.41 17.45 18.49 19.53 20.57
36 2.26 3.55 4.84 6.14 7.43 8.72 10.01 11.30 12.59 13.89 15.18 16.47 17.76 19.05 20.34 21.64 22.93 24.22 25.51
42 2.70 4.24 5.78 7.32 8.86 10.41 11.95 13.49 15.03 16.57 18.11 19.66 21.20 22.74 24.28 25.82 27.36 28.91 30.45
48 3.14 4.93 6.72 8.51 10.30 12.09 13.89 15.68 17.47 19.26 21.05 22.84 24.64 26.43 28.22 30.01 31.80 33.59 35.39
54 3.57 5.61 7.66 9.70 11.74 13.78 15.82 17.86 19.91 21.95 23.99 26.03 28.07 30.11 32.16 34.20 36.24 38.28 40.32
60 4.01 6.30 8.59 10.89 13.18 15.47 17.76 20.05 22.34 24.64 26.93 29.22 31.51 33.80 36.09 38.39 40.68 42.97 45.26
66 4.45 6.99 9.53 12.07 14.61 17.16 19.70 22.24 24.78 27.32 29.86 32.41 34.95 37.49 40.03 42.57 45.11 47.66 50.20
72 4.89 7.68 10.47 13.26 16.05 18.84 21.64 24.43 27.22 30.01 32.80 35.59 38.39 41.18 43.97 46.76 49.55 52.34 55.14
78 5.21 8.19 11.17 14.15 17.13 20.11 23.09 26.07 29.05 32.03 35.01
84 5.65 8.88 12.11 15.34 18.57 21.80 25.03 28.26 31.48 34.71 37.94
90 6.09 9.57 13.05 16.53 20.01 23.48 26.96 30.44 33.92 37.40 40.88
96 6.53 10.26 13.98 17.71 21.44 25.17 28.90 32.63 36.36 40.09 43.82
102 6.96 10.94 14.92 18.90 22.88 26.86 30.84 34.82 38.80 42.78 46.76
108 7.40 11.63 15.86 20.09 24.32 28.55 32.78 37.01 41.23 45.46 49.69
114 7.84 12.32 16.80 21.28 25.76 30.23 34.71 39.19 43.67 48.15 52.63
120 8.28 13.01 17.73 22.46 27.19 31.92 36.65 41.38 46.11 50.84 55.57
EVH-501DINSTALLATION DETAILS
Maximum Size and Installation Information
Model EVH-501D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the installation instructions shown herein.
Model EVH-501D is qualified for installation within concrete/masonry, steel, aluminum or wood substrate. Model EVH-501D is tested and qualified to withstand positive
and negative wind pressure loads up to 130 PSF. The maximum single section width is 120 in. (72 in. height maximum). The maximum single section height is 120 in.
(72 in. width maximum). Multi-wide assemblies are permitted without any additional reinforcing provided the maximum rough opening height is not exceeded. Multi-high
assemblies are permitted provided suitable load bearing structure is provided (by others) at each louver section(s) head and sill condition so that the louver section(s)
may be installed in accordance with the instructions shown herein. Structural reinforcing members along with any associated installation hardware is not provided by
Greenheck unless indicated otherwise by Greenheck. Options and are not subject to structural analysis unless indicated otherwise by Greenheck.
Minimum
Rough Opening Size
12 in� W x 12 in� H
Maximum Rough Opening
Single Section Size
72 3/4 in� W x 120 3/4 in� H or
120 3/4 in� W x 72 3/4 in� H
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
PRODUCT DETAILS EVH-501D
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
FASTENER CHART EVH-501D
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
EVH-501D
September 2021
Copyright © 2021 Greenheck Fan Corporation
Greenheck Fan Corporation reserves the right
to make product changes without notice�
OPTION DRAWINGS EVH-501D
Florida Product Approval No.: 19277.1
Miami-Dade, FL NOA No.: 21-0526.10 EXP. 8/6/2025
AMCA 540 and 550 Listed
Maximum Wind-load: 130 PSF
Finish Type Description/Application Color Selection
Standard Warranty
(Aluminum)
AAMA 2605
100% Fluoropolymer (FEVE)
2-Coat 70% Kynar
®
(PVDF)
3-Coat 70% Kynar
®
(PVDF)
4-Coat 70% Kynar
®
(PVDF)
“Best.” The premier finish for extruded aluminum. Tough,
long-lasting coating has superior color retention and
abrasive properties. Resists chalking, fading, chemical
abrasion and weathering.
Standard Colors:
Any of the 27 standard colors shown can be furnished
in 70% or 50% Kynar
®
, 100% Fluoropolymer or Baked
Enamel.
Mica Colors:
Greenheck offers 6 standard Mica colors for 70%
Kynar
®
or 100% Fluoropolymer.
Custom Colors:
Custom color matching is available. Consult your
Greenheck representative for cost and/or lead-time
implications if a custom color is required.
10 Years
(20 Years Optional)
AAMA 2604
50% Kynar
®
/ Acroflur
®
“Better.” Tough, long-lasting coating has excellent color
retention and abrasive properties. Resists chalking, fading,
chemical abrasion and weathering.
5 Years
AAMA 2603
Baked Enamel
“Good.” Provides good adhesion and resistance to
weathering, corrosion and chemical stain.
1 Year
AA-M10C22A42
Integral Color Anodize
“Two-step” anodizing is produced by following the normal
anodizing step with a second, colorfast process.
Light, Medium, Dark or Extra Dark Bronze;
Champagne; Black
5 years
AA-M10C22A41
Clear Anodize 215 R-1
Clear, colorless and hard oxide aluminum coating that
resists weathering and chemical attack.
Clear 5 years
AA-M10C22A31
Clear Anodize 204
Clear, colorless and hard oxide aluminum coating that
resists weathering and chemical attack.
Clear 1 Year
Prime Coat
Louvers or architectural products shall be cleaned, pre-treated and receive a prime coat finish suitable for field
painting. Greenheck does not recommend prime coat or field painting of materials.
n/a
Mill
Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is acceptable and
there is no concern for color or color change.
n/a
Finishes meet or exceed AAMA 2605, AAMA 2604, and AAMA 2603 requirements. Please consult www.greenheck.com for complete information on standard and
extended paint warranties. Paint finish warranties are not applicable to steel products.
FINISHES